Sale!

Pepperl+Fuchs KFD2-STC4-1 SMART Transmitter Power Supply

  • Model: KFD2-STC4-1
  • Brand: Pepperl+Fuchs
  • Series: K-System Signal Conditioners & Isolated Barriers
  • Core Function: Supplies power to 2-wire SMART transmitters and transfers 4–20 mA signals.
  • Product Type: 1-Channel Transmitter Power Supply / Signal Isolator
  • Key Specs: 24 VDC Power Rail Compatible | 4–20 mA / HART Transparent | 1-Channel Galvanic Isolation
  • Condition: New Original / New Surplus (Never Refurbished)
  • Inventory Status: Active / Essential strategic buffer item for analog instrument loops.
Categories: , , , , SKU: KFD2-STC4-1 Brand:

Description

Key Technical Specifications

Parameter Specification / Value
Manufacturer Pepperl+Fuchs
Part Number KFD2-STC4-1 (Part No. 103562 / 218206)
Signal Type Analog Input (AI)
Number of Channels 1 channel
Power Supply 19–30 VDC via Power Rail or screw terminals
Transmitter Supply Voltage ≥ 16 V at 20 mA (Terminals 1+, 3-)
Input Signal Range 4–20 mA DC
Output Signal Range 4–20 mA DC (Load ≤ 650 Ω)
HART Communication Bi-directional HART signal transparent (0.5 to 40 kHz)
Galvanic Isolation 3-way isolation (Input / Output / Power) up to 250 VAC
Transfer Accuracy ≤ 0.1% of full scale @ 20°C
Operating Temperature −20°C to +60°C (−4°F to +140°F)
Housing & Mounting 20 mm housing width; 35 mm DIN rail mount / Power Rail compatible

 

Product Introduction & Supply Chain Strategy

The Pepperl+Fuchs KFD2-STC4-1 is a 1-channel SMART transmitter power supply and signal conditioner designed for the K-System module family. It feeds power to 2-wire SMART transmitters or current sources in hazardous or safe plant areas, repeating the 4–20 mA current loop signal to control system analog inputs with high galvanic isolation. Built-in HART transparency permits direct pass-through of digital configuration signals from field calibrators to central DCS maintenance stations.

Stocking the KFD2-STC4-1 as New Surplus provides a reliable buffer against field instrument loops going offline during unexpected electrical surges or power dips. Acquiring factory-fresh original surplus avoids the high failure risks of refurbished isolators—such as internal component drift, degraded isolation transformers, and erratic HART handshakes—ensuring immediate drop-in replacement and maintaining low total cost of ownership across process operations.

KFD2-STC4-1

KFD2-STC4-1

KFD2-STC4-1

KFD2-STC4-1

Installation & Configuration Guide

1.Pre-Installation Preparation:Prerequisite & Safety Prep.

Verify that loop power to the 24 VDC cabinet distribution rail is turned off or isolated. Put on a grounded ESD wrist strap before handling the module. Document the existing wiring connections and check terminal numbering against your loop drawing before removing any field wires.

2.Module Removal from DIN Rail:Mechanical Extraction.

Disconnect the removable screw terminal blocks by lifting them gently out of the module housing. Insert a small flathead screwdriver into the red DIN rail locking tab at the bottom of the module, pull down to release the latch, and pivot the module off the DIN rail or Power Rail.

3.Installation on DIN / Power Rail:Mounting & Seating.

Hook the top groove of the new KFD2-STC4-1 onto the top edge of the 35 mm DIN rail or Power Rail. Push the bottom of the housing firmly toward the rail until the red locking clip snaps into place. Reinsert the pre-wired removable terminal blocks into their corresponding terminal positions on the top and bottom of the module.

4.Power-On & Signal Diagnostics:Loop Verification.

Re-apply 24 VDC power to the Power Rail or supply terminals. Verify that the front-panel green Power LED lights up solid. Use a multimeter or HART communicator to check that the 4–20 mA current loop is passing accurately and that digital communication with the field transmitter is fully established.

 

Firmware/Software Versions & Upgrade Notes

  • Hardware Compatibility: Fully compatible with all standard 35 mm DIN rail environments and Pepperl+Fuchs K-System 3-wire or 5-wire Power Rails.
  • HART Pass-Through: The KFD2-STC4-1 operates as a purely hardware-based analog signal isolator with passive HART pass-through. It requires no software downloads, DIP switch programming, or firmware updates.
  • Wiring Configurations: Verify whether your transmitter is a 2-wire active loop power device or a 3-wire/4-wire powered source. Terminal wiring varies between current sink and current source modes (e.g., Terminals 1+/3- for 2-wire vs. Terminals 2+/3- for current sources).

 

Frequently Asked Questions (FAQ)

Why is New Surplus preferred over refurbished signal isolators for process loops?

Refurbished signal conditioners often suffer from degraded internal isolation transformers, aging optocouplers, and thermal drift, leading to inaccurate 4–20 mA signal transmission. In critical loops, a drifted signal can trigger erroneous valve trips or improper burner controls. Our New Surplus KFD2-STC4-1 units are 100% factory-fresh and uninstalled, ensuring original measurement accuracy and full isolation ratings.

How do you confirm this Pepperl+Fuchs module is original and unused?

Every unit undergoes a strict inbound verification process. We check for original Pepperl+Fuchs factory packaging, pristine terminal screw contacts with zero insertion marks, flawless enclosure housing, and perform electrical continuity and isolation testing before shipment. A complete QC report is included with each order.

Can the pass digital HART communicator signals to field transmitters?

Yes. The is fully HART-transparent. It allows bi-directional HART communication signals (0.5 to 40 kHz) to pass overlaid on the 4–20 mA analog signal without attenuation, enabling remote configuration via hand-held calibrators or asset management software.

What is the difference between mounting this on a standard DIN rail vs. a Power Rail?

The can be mounted on a standard 35 mm DIN rail with manual wiring to its power terminals, or snapped onto a Pepperl+Fuchs Power Rail. When mounted on a Power Rail, the module automatically draws its 24 VDC supply from the rail bus, reducing panel wiring and simplifying hot-swapping during maintenance.

What warranty is provided with this New Surplus isolator?

We back this New Surplus Pepperl+Fuchs signal isolator with a full 1-year functional replacement warranty. If any operational defect occurs under normal working conditions within 12 months, we provide an immediate direct replacement or full refund.