The Phoenix Contact PLC-RSC-24UC/21 (Order / Part Number: 2966184) is a slim-profile electromechanical relay module designed for industrial control, automation, and signal-matching architectures. Part of the widely deployed PLC-INTERFACE product family, this unit consists of a basic screw-connection terminal block and a plug-in miniature power contact relay. It provides reliable signal isolation between field instrumentation and control-level hardware.
Engineered to operate on a nominal input voltage of 24 V AC/DC, the module integrates an internal bridge rectifier and a yellow LED operating voltage indicator. It features a single changeover (SPDT / 1 PDT) contact configuration capable of switching up to 250 V AC/DC, housed in a space-saving 6.2 mm wide industrial enclosure built for standard DIN rail mounting.
Key Technical Specifications
| Parameter | Specification |
| Brand | Phoenix Contact |
| Model Series | PLC-INTERFACE (PLC-RSC) |
| Base Model / Order Code | PLC-RSC-24UC/21 (2966184) |
| Module Type | Electromechanical Relay Terminal Block Module |
| Nominal Input Voltage | 24 V AC/DC |
| Input Voltage Range | 19.4 V AC/DC to 33.6 V AC/DC (at 20°C) |
| Typical Input Current | 11 mA (at 24 V AC) / 8.5 mA (at 24 V DC) |
| Contact Configuration | 1 changeover contact (SPDT / 1 PDT) |
| Contact Material | AgSnO (Silver Tin Oxide) |
| Maximum Switching Voltage | 250 V AC/DC |
| Limiting Continuous Current | 6 A |
| Status Indicator | Yellow LED (Operating voltage display) |
| Connection Method | Screw Connection |
| Width | 6.2 mm |
| Operating Temperature Range | -40°C to 60°C |
Detailed Product Overview
The Phoenix Contact PLC-RSC-24UC/21 functions as an essential electrical interface bridge in industrial control panels. It effectively decouples sensitive PLC or controller input/output channels from high-voltage field loads, preventing back-feed surges, ground loops, and electrical noise from damaging processor cards.
The modular assembly combines a secure screw terminal base (PLC-BSC) with a replaceable miniature electromechanical relay (REL-MR). The inclusion of a built-in bridge rectifier permits seamless handling of both alternating and direct current (AC/DC) control signals at 24V. Its ultra-slim 6.2 mm housing profile maximizes DIN rail packing density in crowded control cabinets, while plug-in bridging options allow fast potential distribution across multiple adjacent modules.
Dimensions, Mounting & Connection Notes
- Mounting Position: Vertical or horizontal on standard NS 35 DIN rails.
- Conductor Cross-Section: Supports rigid and flexible wires from 0.14 mm² to 2.5 mm² (AWG 26–14).
- Terminal Tightening Torque: 0.5 to 0.6 Nm recommended for screw clamp connections.
Engineering Selection Highlights
- Universal AC/DC Compatibility: Accepts 24V AC or DC control signals, minimizing variant stock requirements across mixed power control panels.
- Ultra-Slim Profile: Space-saving 6.2 mm width saves valuable DIN rail space in high-density I/O integration applications.
- Plgable Relay Architecture: Allows fast, tool-free replacement of the internal relay element without disconnecting field wiring terminals.
- Built-in Protection and Indication: Features an integrated input circuit with interference suppression, a protective bridge rectifier, and a clear yellow status LED.

PLC-RSC-24UC
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
| DIN Rail Mounting | NS 35/7.5 or NS 35/15 Standard DIN Rails | Standard snap-on installation. |
| Potential Bridging | Phoenix Contact FBST 6-PLC… Plug-in Bridges | Used for fast power-rail distribution across adjacent modules. |
| System Cabling Adapter | Phoenix Contact V8 System Adapter | Optional interface adapter for rapid flat-cable connection to PLC output cards. |
| Partition Plates | PLC-ATP Partition Plate | Required between adjacent modules when switching voltages greater than 250V (L1, L2, L3). |
FAQ
What is the function of the Phoenix Contact PLC-RSC-24UC/21?
It is an electromechanical relay module utilized for galvanic isolation, signal conversion, and power amplification between industrial controllers and field devices.
What input voltage does this module accept?
It accepts a nominal input voltage of 24 V AC/DC (operating reliably within a 19.4V to 33.6V range).
What does the “-RSC” designation mean?
“RSC” designates the Relay type with Screw Connection technology. (Modules with tension-clamp connections are designated as RT).
Can the internal relay be replaced if it fails?
Yes. The modular design features a plug-in miniature relay mounted inside the screw terminal base block, allowing replacement without rewiring.
Verification & Troubleshooting Notes
- Relay Fails to Energize (LED Off): Check that the 24 V AC/DC control signal is actively present across terminals A1 and A2, and verify that the polarity (for DC) or voltage amplitude meets the minimum 19.4V threshold.
- No Output Continuity: Inspect downstream load circuits and verify that the maximum switching current does not exceed the 6 A continuous limit. Ensure the plug-in relay is firmly pushed down into its base socket.
- Intermittent Switching Issues: Verify secure wire tightening at the screw terminals (0.5–0.6 Nm) and check for excessive vibration or environmental moisture inside the control cabinet.