Sale!

ProSoft PLX31-EIP-ASCII4 EtherNet/IP to 4-Port ASCII Gateway

Parameter Specification
Brand ProSoft Technology
Model / Part Number PLX31-EIP-ASCII4
Device Type EtherNet/IP to 4-Port ASCII Communication Gateway
Supported PLC Types Rockwell Automation ControlLogix, CompactLogix, PLC-5, SLC 500, MicroLogix, and select Schneider Electric controllers
Ethernet Port 10/100Mbit full/half-duplex RJ45 connector
Number of Serial Ports 4 independent ports
Serial Port Isolation 2500 Vrms port signal isolation (per UL 1577)
Data Buffer Size 255-byte transmit buffer with configurable character delays
Power Supply Requirements 24 VDC nominal (10 to 36 VDC allowed)
Current Load 300 mA at 24 VDC nominal (610 mA max)
Operating Temperature -25°C to 70°C (-13°F to 158°F)
Enclosure Dimensions 5.38 x 1.99 x 4.38 in (13.67 x 5.05 x 11.13 cm)
Categories: , , , , SKU: PLX31-EIP-ASCII4 Brand:

Description

Core Product Summary (Brand / Model / Key Attributes)

The ProSoft Technology PLX31-EIP-ASCII4 is a high-performance communication gateway designed to link EtherNet/IP-enabled programmable automation controllers (PACs) with up to four independent serial ASCII devices, such as barcode readers, weigh scales, printers, and RFID systems.

The gateway supports bidirectional data transfers, utilizing high-speed Class 1 I/O connections or Class 3 explicit messaging. It features an embedded EDS Add-On Profile for streamlined configuration within Rockwell Automation environments (such as ControlLogix and CompactLogix), an integrated SD card slot for disaster recovery, and four optically isolated serial communication ports.

 

Key Technical Specifications

Parameter Specification
Brand ProSoft Technology
Model / Part Number PLX31-EIP-ASCII4
Device Type EtherNet/IP to 4-Port ASCII Communication Gateway
Supported PLC Types Rockwell Automation ControlLogix, CompactLogix, PLC-5, SLC 500, MicroLogix, and select Schneider Electric controllers
Ethernet Port 10/100Mbit full/half-duplex RJ45 connector
Number of Serial Ports 4 independent ports
Serial Port Isolation 2500 Vrms port signal isolation (per UL 1577)
Data Buffer Size 255-byte transmit buffer with configurable character delays
Power Supply Requirements 24 VDC nominal (10 to 36 VDC allowed)
Current Load 300 mA at 24 VDC nominal (610 mA max)
Operating Temperature -25°C to 70°C (-13°F to 158°F)
Enclosure Dimensions 5.38 x 1.99 x 4.38 in (13.67 x 5.05 x 11.13 cm)

 

Detailed Product Overview

The ProSoft PLX31-EIP-ASCII4 acts as a dedicated translator between modern industrial Ethernet backbones and legacy or specialized serial equipment requiring string data formats. By incorporating four distinct serial ports onto a single hardware module, it reduces hardware footprints and minimizes wiring complexity in applications that aggregate data from multiple peripheral instruments.

The module allows up to 10,000 16-bit registers to be used for exchanging large data blocks between connected serial hardware and the plant controller. Configuration parameters are managed through ProSoft Configuration Builder (PCB) and can be saved to an optional local SD card, allowing fast module swaps and zero-configuration disaster recovery replacement in the field.

PLX31-EIP-ASCII4

PLX31-EIP-ASCII4

PLX31-EIP-ASCII4

PLX31-EIP-ASCII4

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Controller Platform Rockwell Automation ControlLogix / CompactLogix (Logix5000 family) Utilizes Add-On Profiles (AOP) for simplified integration.
Power Input 24 VDC Nominal (10 to 36 VDC acceptable) Use the included J180 4-position power connector terminal block.
Serial Interfacing RS-232, RS-422, or RS-485 physical layers Shipped with RJ45-to-DB9 adapter cables and screw terminal blocks.
Configuration Tool ProSoft Configuration Builder (PCB) software Requires an active Ethernet connection to the module for initial setup or diagnostics.

 

Engineering Selection Highlights

  • Multi-Port Integration: Four independent serial channels minimize hardware count when gathering data from multiple separate ASCII peripherals.
  • Seamless Rockwell Integration: Native EDS Add-On Profiles and support for standard Studio 5000 / RSLogix environments streamline tag mapping and setup.
  • Robust Signal Isolation: 2500 Vrms optical/RF isolation on serial ports safeguards electronics against ground loops and electrical noise.
  • Flexible Data Exchange: Supports both scheduled I/O (Class 1) and unscheduled messaging (Class 3) options to tune network bandwidth usage.

 

Dimensions, Mounting & Connection Notes

  • Physical Dimensions: 13.67 cm x 5.05 cm x 11.13 cm (5.38 in x 1.99 in x 4.38 in).
  • Mounting Style: Standard DIN rail mount designed for industrial control panels.
  • Diagnostics: Front-panel LED array displays power state, hardware health, network status (NS/MS), and individual TX/RX activity for all four serial channels.

 

FAQ

What is the primary function of the ProSoft PLX31-EIP-ASCII4?

It serves as a high-speed protocol gateway connecting EtherNet/IP-based controllers to up to four independent serial ASCII devices, such as barcode scanners or weigh scales.

How many serial ports does the module feature?

The module is equipped with four independent configurable serial communication ports.

Is an SD card required for operation?

No, the SD card is optional; it is primarily used for storing configuration files to facilitate quick disaster recovery and parameter backups.

What software is used to configure the gateway?

Configuration is handled via ProSoft Technology’s ProSoft Configuration Builder (PCB) software utility.

 

Verification & Troubleshooting Notes

  • Module Fault (FLT / ERR LEDs Active): Check power supply voltage stability (must stay within the 10 to 36 VDC range) and verify that the Ethernet IP address settings match the intended network subnet.
  • No Serial Data Transmission (TX/RX LEDs Dark): Verify physical wiring, baud rates, parity, data bits, and stop bits match between the gateway port configuration and the connected field device. Ensure the correct RJ45-to-DB9 adapter layout is utilized.
  • Ethernet Communication Dropouts: Confirm that the requested packet interval (RPI) settings on Class 1 I/O connections are tuned correctly and do not flood the network bandwidth.