Sale!

Schneider Electric NW-BM85C002 Modicon BM85 Modbus Plus Bridge

  • Model: NW-BM85C002
  • Brand: Schneider Electric (Modicon)
  • Series: Modicon BM85 Bridge/Multiplexer family
  • Core Function: Bridges serial Modbus devices to Modbus Plus networks
  • Product Type: Network Bridge / Multiplexer (communication gateway)
  • Key Specs: 4× RS-232 serial ports, Modbus ASCII/RTU (300–19,200 baud), single or dual Modbus Plus network cables
  • Power: 115/230 Vac or 24 Vdc, 10 W
  • ⚠️ Obsolete Model — Limited Stock Available (superseded the NW-BM85-000; no longer in active production)
  • Condition: New Original / New Surplus
Categories: , , , , SKU: NW-BM85C002 Brand:

Description

Key Technical Specifications

Parameter Value
Manufacturer Schneider Electric (Modicon)
Part Number NW-BM85C002
Product Type BM85 Bridge/Multiplexer module
Network Protocol Modbus Plus (single- or dual-cable)
Serial Ports 4× DB9S (RS-232)
Serial Protocol Modbus, ASCII or RTU
Serial Baud Rate 300–19,200 baud
Parity / Stop Bits Odd/even/no parity; 1 or 2 stop bits
Power Supply 115/230 Vac (+15%, 47–63 Hz) or 24 Vdc (+15%)
Power Consumption 10 W
Mounting Panel/rack, vertical or horizontal, with brackets
Dimensions 2.59 in H × 11.50 in W (14.08 in with brackets) × 8.30 in D
Weight 5.5 lb (2.5 kg)
Storage Temperature −40 to +80 °C
Humidity 0–95%, non-condensing
Max Altitude 10,000 ft (3 km)
EMI Susceptibility MIL STD 461B RS03 / CS03
Network Segment Limit 32 nodes without repeater; 64 with repeaters

 

Product Introduction

The Schneider Electric NW-BM85C002 is a Modicon BM85 bridge/multiplexer that connects up to four RS-232 Modbus devices to a Modbus Plus network. Plants use it to link legacy Modbus ASCII/RTU equipment — drives, HMIs, meters — into Quantum and 984-series PLC architectures, with each serial port independently configurable from 300 to 19,200 baud. (Reference document: Modicon 890 USE 103 00.)

This unit replaced the earlier NW-BM85-000 and adds dual-cable Modbus Plus redundancy, a real advantage on segments where a single cable break would stop production. It routes traffic between serial ports on the same unit and across other BM85s on the network, so one module often eliminates several point-to-point serial runs. If you’re maintaining a Modicon Modbus Plus installation, this is the standard gateway — verify against your OEM manual (890 USE 103 00) before committing to the swap.

 

Troubleshooting Quick Reference

Symptom Possible Cause Relevance to this Part Quick Check Method Recommendation
No LEDs on power-up Power supply failure / blown fuse ❌ Low Measure 115/230 Vac or 24 Vdc at the rear-panel power connector with a multimeter; check the ON/OFF switch position Fix supply and fuses before replacing the unit
All serial ports dead, network LED normal Unit internal fault ✅ High Ping the module’s Modbus Plus node address from another node; check serial port status LEDs Module likely needs replacement
Communications drop intermittently Cable/termination fault on Modbus Plus segment ❌ Low Verify 120 Ω termination at both segment ends; check Belden 986 (or equivalent) cable for damage; confirm ≤32 nodes per 450 m segment Repair cabling — this part is usually not the culprit
One serial port unresponsive, others fine Bad RS-232 cable or RTS/CTS handshake issue ❌ Low Check that RTS (pin 7) is jumpered to CTS (pin 8) on slave-port cables; test with a known-good serial cable Re-terminate cable before suspecting the module
Wrong data / garbage characters Baud/parity mismatch after module swap ✅ High Compare port config against the old unit’s settings; confirm ASCII vs RTU mode and 300–19,200 baud settings Reconfigure the port — the hardware is fine
Node not seen on Modbus Plus network Duplicate or wrong node address ✅ High Check the module’s configured node address; scan for address conflicts across all 64 possible nodes Correct the address; no hardware swap needed

Honest note: in field service, BM85 failures are far more often cabling, termination, or configuration problems than dead modules. If you’re stuck after these checks, contact technical support with photos of the unit, LED states, and the diagnostic/event log — we’ll help you isolate it before you spend money on a replacement.

NW-BM85C002

NW-BM85C002

NW-BM85C002

NW-BM85C002

Frequently Asked Questions

Q1: Is the NW-BM85C002 a direct replacement for the NW-BM85-000?
Yes. Modicon superseded the NW-BM85-000 with the NW-BM85C002. The C002 supports single- AND dual-cable Modbus Plus networks, where the -000 was single-cable only. Both have four DB9S serial ports. One caveat: back up your old unit’s port configurations before pulling it, because you’ll need to recreate them — settings don’t transfer themselves.

Q2: Can I hot-swap this module?
No. The BM85 is a powered network device, not a backplane I/O card, but the same rule applies — kill the power and isolate it from the network first. Pulling a live unit mid-transaction can corrupt communication sessions and cause a false failure alarm across every node it bridges. Power down, swap, power up, then verify node address and port settings before returning it to service.

Q3: What condition is this unit in, and why is it cheaper than buying from the factory?
This listing is for New Original / New Surplus stock — genuine Schneider Electric product, unused, but sourced through surplus channels rather than new production. Schneider no longer actively builds this model, so factory-fresh supply is essentially gone. We verify every unit: serial number check against OEM records, visual inspection, full power-up on our in-house Modicon test bench, handshake tests on all four serial ports, a Modbus Plus network join test, and a 24-hour continuous-run burn-in with thermal checks. Test reports, photos, and videos are available on request. It’s cheaper because surplus inventory works that way — the hardware is identical, the supply chain isn’t.

Q4: What warranty do you offer?
A 1-year replacement warranty covering functional failure under normal operating conditions (115/230 Vac or 24 Vdc supply, −40 to +80 °C storage, 0–95% non-condensing humidity, per the 890 USE 103 00 spec). Damage from miswiring, wrong supply voltage, or lightning/power surges isn’t covered — and honestly, on a legacy bridge, supply voltage errors are the most common killer. Verify your power source before energizing.

Q5: Will my configuration survive a module swap?
No — and this trips people up constantly. The BM85 stores port settings in the unit itself. Take photos of the front-panel settings, or better, save the configuration through the software tool BEFORE you disconnect anything. I’ve seen techs swap a BM85 in under ten minutes and then spend two days rebuilding port configs from memory because nobody documented the old one. Don’t be that person. Photograph everything first.

Q6: What do I need for a clean installation?
Check three things. First, node address — make sure your configured Modbus Plus address doesn’t conflict with an existing node. Second, termination — 120 Ω resistors at both physical ends of the segment (Modicon PN 990NAD97110 or equivalent), no more than 32 nodes per 450 m segment without a repeater. Third, serial handshake — on slave ports, RTS (pin 7) must be jumpered to CTS (pin 8) or the port will sit silent and you’ll chase a ghost. Belden 986 or equivalent Modbus Plus rated cable only; regular serial cable will give you intermittent errors you’ll never fully run down.

Q7: Do you ship internationally, and how fast?
Yes — in-stock units ship within 1–2 business days via DHL, FedEx, or UPS, worldwide. Each unit leaves in an anti-static bag, bubble-wrapped, in a heavy-duty corrugated box, with a QC Passed label and inspection date. Because this model is discontinued, stock is limited and availability changes weekly. If you have a critical outage, call us directly — we’ll confirm physical stock before you commit to the order.