SEG XU2-AC Digital AC Voltage Protection Relay

The SEG XU2-AC is a digital measuring relay for AC voltage supervision in two-, three-, and four-wire electrical systems. It protects generators, consumers, and general electrical equipment against unacceptable overvoltage and undervoltage conditions and can also supervise phase sequence.

Categories: , , , , SKU: XU2-AC Brand:

Description

Core Product Summary

The SEG XU2-AC is a digital measuring relay for AC voltage supervision in two-, three-, and four-wire electrical systems. It protects generators, consumers, and general electrical equipment against unacceptable overvoltage and undervoltage conditions and can also supervise phase sequence.

The relay provides independent overvoltage and undervoltage functions with separately adjustable pickup values, tripping periods, and switching hysteresis. It measures phase-to-neutral or phase-to-phase voltage, supports 50 Hz or 60 Hz systems, and includes two output relays, each with one changeover contact. The XU2-AC is DIN-rail mounted and includes an integrated self-test function.

 

Key Technical Specifications

Category Specification
Product type Digital AC voltage protection relay
Product family SEG Professional Line
Protection functions Undervoltage, overvoltage, phase-sequence supervision
ANSI device functions 27 undervoltage; 59 overvoltage
System types Two-, three-, and four-wire systems
Voltage measurement Phase-to-neutral or phase-to-phase
Nominal voltage settings 100 V, 110 V, 230 V, or 400 V AC
Frequency range 35–78 Hz
Frequency setting 50 Hz or 60 Hz by DIP switch
Undervoltage setting range 75–105% of Un, continuously adjustable
Overvoltage setting range 95–125% of Un, continuously adjustable
Trip delay setting ranges 0–1 s or 0–10 s, continuously adjustable
Hysteresis settings 3%, 6%, or 10%
Output relays 2
Relay contacts 1 changeover contact per trip relay
Auxiliary supply, low range 19–55 VDC at terminals A1 and A2; 3 W
Auxiliary supply, wide range 50–750 VDC or 36–520 VAC at terminals A1 and A3; approximately 4 W
Reset time from pickup Less than 50 ms
Return time from trip 500 ms
Minimum initialization time 100 ms after supply voltage is applied
Minimum response time 50 ms when supply voltage is available
Time-lag error Class index E, ±20 ms
Mounting DIN rail to DIN EN 50022
Self-test Integrated, activated by pushbutton
Standards IEC 60255-1

 

Engineering Selection Highlights

  • The XU2-AC provides both undervoltage and overvoltage protection in one relay, making it suitable for generator, transformer, motor, cable, overhead-line, and busbar supervision.
  • Its selectable 100 V, 110 V, 230 V, or 400 V nominal voltage setting must match the connected voltage-transformer secondary or measured system voltage.
  • The relay supports phase-to-neutral or phase-to-phase measurement, allowing it to be applied to different wiring configurations.
  • Independent pickup values, trip delays, and hysteresis for overvoltage and undervoltage allow the protection response to be coordinated with the application.
  • Phase-sequence supervision can be enabled or disabled, which is relevant for rotating machines and systems where correct phase rotation is required.
  • Two changeover output relays provide trip signaling or control actions.
  • The wide-range auxiliary supply accepts 36–520 VAC or 50–750 VDC, allowing the relay to be powered from the measured voltage or a separate secured auxiliary supply.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Electrical system Two-, three-, and four-wire AC systems The relay supervises system voltage and, where enabled, phase sequence.
Voltage inputs L1, L2, L3, and N terminals Supports phase-to-neutral or phase-to-phase voltage measurement.
Nominal voltage 100 V, 110 V, 230 V, or 400 V AC Set with the front-panel DIP switches.
System frequency 35–78 Hz; 50 Hz or 60 Hz selection Frequency is selected by DIP switch.
Auxiliary supply 19–55 VDC or 36–520 VAC / 50–750 VDC Select the appropriate A1/A2 or A1/A3 terminal arrangement.
Output circuits 2 changeover relay contacts Use for trip indication, alarms, or control actions.
Parameter setting Front-panel DIP switches and potentiometers Nominal values, functions, pickup values, delays, and hysteresis are set locally.
Configuration software SEG Smart view operating software A full version is included for downloading.
Mounting DIN rail to DIN EN 50022 The relay is designed for DIN-rail installation.

 

Dimensions, Mounting & Connection Notes

Item Verified data
Mounting method DIN-rail mounting to DIN EN 50022
Front panel Sealable
Operating elements DIP switches, potentiometers, display elements, and self-test pushbutton
Voltage input terminals L1, L2, L3, and N
Auxiliary supply terminals A1/A2 for 19–55 VDC; A1/A3 for 36–520 VAC or 50–750 VDC
Output relays 2 changeover contacts
Power consumption 3 W at 19–55 VDC; approximately 4 W at A1/A3
Front-panel configuration Local adjustment without disconnecting the relay
Self-test Integrated pushbutton-initiated self-test

 

Detailed Product Overview

The SEG XU2-AC is a digital measuring relay for AC voltage protection in two-, three-, and four-wire systems. It provides independent undervoltage and overvoltage supervision, each with separately adjustable pickup values and tripping periods. The relay also supports phase-sequence supervision, which can be switched on or off according to the application.

Voltage signals are connected through L1, L2, L3, and N terminals. The relay can measure phase-to-neutral or phase-to-phase voltage. Nominal voltage is selected as 100 V, 110 V, 230 V, or 400 V using front-panel DIP switches. The relay operates across a 35–78 Hz frequency range, with 50 Hz or 60 Hz selected by DIP switch.

The undervoltage setting range is 75–105% of nominal voltage, while the overvoltage setting range is 95–125% of nominal voltage. Trip delays are continuously adjustable over 0–1 s or 0–10 s ranges. Hysteresis can be set to 3%, 6%, or 10%, affecting the dropout-to-pickup relationship. The documented time-lag error is class index E, ±20 ms.

The XU2-AC includes two trip relays, each providing one changeover contact. These outputs can be used for trip signaling, alarms, or control actions. The relay’s front panel contains all operating and display elements needed for local adjustment, allowing settings to be changed without disconnecting the unit. The front panel is sealable.

The relay has an integrated wide-range power supply. It can be powered from the measured quantity or from a secured auxiliary supply. Terminals A1 and A2 accept 19–55 VDC and consume 3 W. Terminals A1 and A3 accept 36–520 VAC or 50–750 VDC and consume approximately 4 W.

The XU2-AC is designed for DIN-rail mounting according to DIN EN 50022. It includes an integrated self-test function activated by a pushbutton and meets the requirements of IEC 60255-1. A full version of SEG’s Smart view operating software is included for downloading.

XU2-AC

XU2-AC

XU2-AC

XU2-AC

Applications & System Role

The XU2-AC is a voltage-protection relay in generation, distribution, and industrial electrical systems. It monitors system voltage and initiates a trip output when voltage moves outside the configured overvoltage or undervoltage limits.

The relay can protect generators, consumers, and general equipment against inadmissible voltage conditions. Its phase-sequence supervision function adds protection for systems where incorrect phase rotation could affect motors, generators, or other rotating equipment.

Typical fit scenarios include generator protection, transformer and switchgear supervision, motor and cable protection, and busbar voltage monitoring in low- or medium-voltage systems.

 

FAQ

What is the SEG XU2-AC?
The SEG XU2-AC is a digital AC voltage protection relay for overvoltage, undervoltage, and phase-sequence supervision in two-, three-, and four-wire electrical systems.

Which protection functions does the XU2-AC provide?
It provides undervoltage protection (ANSI 27), overvoltage protection (ANSI 59), and switchable phase-sequence supervision.

What nominal voltages can the XU2-AC be set for?
The relay can be set for 100 V, 110 V, 230 V, or 400 V AC nominal voltage using front-panel DIP switches.

What are the voltage setting ranges?
Undervoltage is adjustable from 75–105% of nominal voltage, and overvoltage is adjustable from 95–125% of nominal voltage.

How many output relays does the XU2-AC have?
It has two trip relays, each with one changeover contact.

What auxiliary supply voltages does the XU2-AC accept?
It accepts 19–55 VDC at terminals A1/A2, or 36–520 VAC / 50–750 VDC at terminals A1/A3.

Can the XU2-AC monitor phase sequence?
Yes. Phase-sequence supervision is available and can be switched on or off.

How is the XU2-AC mounted?
It is designed for DIN-rail mounting according to DIN EN 50022.