Sale!

Siemens POL688.10/STD Climatix C600 HVAC&R Controller

Item Verified Information
Manufacturer / product family Siemens, Climatix C600
Exact model POL688.10/STD
Siemens stock number S55396-C881-A100
Product type Freely programmable HVAC&R controller
Physical I/O count 27 inputs and outputs
Universal inputs 3 (X9, X10, X11)
Universal inputs/outputs 8 (X1–X8)
Categories: , , , , SKU: POL688.10/STD Brand:

Description

Core Product Summary

The Siemens POL688.10/STD, stock number S55396-C881-A100, is a Climatix C600 freely programmable controller for heating, ventilation, air-conditioning and refrigeration equipment. It provides 27 physical inputs and outputs, along with onboard Ethernet, RS-485, KNX process-bus, SD-card and USB interfaces.

The controller operates from AC 24 V or DC 24 V and supports Modbus, BACnet, PL-Link, JSON and OPC UA communication. Its I/O set includes three universal inputs, eight universal inputs/outputs, six digital inputs, eight relay outputs and two triac outputs, making it suitable for machine-level control and monitoring in HVAC&R applications.

 

Key Technical Specifications

Item Verified Information
Manufacturer / product family Siemens, Climatix C600
Exact model POL688.10/STD
Siemens stock number S55396-C881-A100
Product type Freely programmable HVAC&R controller
Physical I/O count 27 inputs and outputs
Universal inputs 3 (X9, X10, X11)
Universal inputs/outputs 8 (X1–X8)
Digital inputs 6 (D1, D2, DU1, DU2, DL1, DL2)
Relay outputs 8 (Q1–Q8)
Triac outputs 2 (DO1, DO2)
Supply voltage AC 24 V, -20% to +20%; DC 24 V, ±10%
Supply frequency 45–65 Hz
Power consumption 39 VA / 24 W without extension modules
Current consumption Max. 1.6 A at AC 24 V; max. 1.0 A at DC 24 V
Processor ARM Cortex M4, 120 MHz
Memory 64 MB SDRAM; 64 MB flash
Weight 468 g
Ingress protection IP20
Operating temperature -40 to 70 °C, with documented restrictions for communication modules and LCD use

 

Engineering Selection Highlights

  • Exact Climatix C600 fit: POL688.10/STD is the non-HMI version of the 27-I/O Climatix C600 controller, so it suits applications that use a remote HMI or do not require an integrated operator display.
  • Mixed signal handling: Its three universal inputs and eight configurable universal I/O channels support NTC, Ni1000, Pt1000, resistance, voltage and current signals, allowing sensors and analog devices to be integrated without a separate signal-conditioning layer in many applications.
  • Relay and triac capacity: Eight relay outputs and two triac outputs provide direct control of loads such as fans, dampers, heaters and other HVAC actuators, subject to the documented contact ratings and external protection requirements.
  • Building-system integration: Ethernet, galvanically separated RS-485, non-isolated RS-485 and KNX-based process-bus interfaces support Modbus, BACnet, PL-Link and other Siemens device networking options.
  • Programming and service access: SAPRO is used for application programming, while SCOPE and the USB service interface support commissioning and diagnostics; the SD-card interface can load applications and firmware.
  • Expansion capability: The controller supports up to 31 Climatix I/O extension modules and up to two communication modules, so I/O count and protocol coverage can be expanded when the application requires it.
  • Cabinet installation requirement: The IP20 housing requires installation in a protective enclosure, and SELV/PELV wiring must not be mixed with mains-voltage wiring on the same terminal block.

 

Detailed Product Overview

The Siemens POL688.10/STD is a Climatix C600 controller designed for HVAC&R machines that require a configurable combination of sensor inputs, actuator outputs and building-automation connectivity. With 27 physical I/O points, it provides a larger local I/O capacity than the 21-I/O POL648 models while remaining a non-HMI controller; the POL688.80/STD variant adds an integrated display.

Its input architecture is built around three universal inputs and eight universal inputs/outputs. These channels can be configured for common HVAC sensor types, including NTC10k and NTC100k thermistors, Ni1000 and Pt1000 resistance sensors, resistance inputs, DC voltage inputs and current inputs. The controller also provides dedicated digital-input groups: two potential-free inputs, two 24 V active inputs, and two 115–230 V active inputs. This range allows temperature, pressure, status, flow, pulse and line-voltage status signals to be brought into one controller.

On the output side, the POL688.10/STD includes eight relay outputs and two triac outputs. The relay outputs provide both NO and NC capability on Q1 and Q2, while Q3 through Q8 are NO outputs. The triac outputs are intended for AC actuator loads and require external protection. The universal I/O channels can also be configured as 0–10 V, 0–20 mA, 24 V DC or PWM outputs, giving the application programmer flexibility in matching output types to valves, dampers, frequency converters and other field devices.

Communication is a central feature of the controller. The onboard Ethernet port supports Modbus IP, BACnet IP, OPC UA, SNMP, JSON, HTTP, FTP and SNTP, depending on the required function and licensing. Two RS-485 ports support Modbus RTU and, on the galvanically separated T6 port, BACnet MS/TP. The process bus supports KNX TP1-based PL-Link communication with Siemens controllers and room units. Additional communication modules can extend the system to LON, M-Bus and further Modbus or BACnet options.

The controller is programmed using Siemens SAPRO and commissioned or diagnosed with SCOPE. Applications and firmware can be loaded through the SD-card interface, and the USB service interface provides tool access. The POL688.10/STD has 64 MB of SDRAM and 64 MB of flash memory, with an ARM Cortex M4 processor running at 120 MHz.

Installation requires a protective enclosure because the housing is IP20. The controller accepts AC 24 V or DC 24 V power, consumes up to 39 VA or 24 W without extension modules, and requires external supply-line protection. When expanding the system, the power budget must account for connected I/O modules, and the documented limits on bus lengths, cable types and terminal segregation should be observed.

POL688.10/STD

POL688.10/STD

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Controller family Siemens Climatix C600 The POL688.10/STD is a 27-I/O member of the C600 controller range.
Power supply AC 24 V or DC 24 V Use an external maximum 4 A non-renewable fuse or type B, C or D circuit breaker in the supply line.
Sensor inputs NTC10k, NTC100k, Ni1000, Pt1000, resistance, DC voltage, current Universal inputs and universal I/O channels are software-configurable.
Analog outputs DC 0–10 V and 0–20 mA Available on the universal I/O channels according to the documented configuration.
Digital outputs Relays and triacs Relay outputs Q1–Q8 and triac outputs DO1–DO2 require external protection for inductive loads.
Ethernet integration Modbus IP, BACnet IP, OPC UA, SNMP, JSON, HTTP, FTP, SNTP The Ethernet port supports engineering tools, cloud integration and building-management-system communication.
RS-485 integration Modbus RTU and BACnet MS/TP T6 is galvanically separated; T14 is not galvanically separated.
Process bus KNX TP1 / PL-Link Used to connect Climatix controllers and room units.
HMI Remote Climatix HMI via RJ45 / RS-485 The POL688.10/STD does not include an integrated HMI.
Programming tools SAPRO and SCOPE Applications are created in SAPRO; SCOPE supports commissioning and diagnostics.
I/O expansion Up to 31 Climatix I/O extension modules Connected through the peripheral bus; power-budget limits apply.
Communication expansion Up to two communication modules Supported protocols include Modbus RTU, BACnet MS/TP, LON, M-Bus, BACnet IP and Modbus IP, depending on module.

 

Applications & System Role

The POL688.10/STD is positioned as a machine-level controller in HVAC&R systems. It reads field sensors, executes a programmable control application, and operates actuators and loads through its analog, relay and triac outputs.

Typical system roles include controlling and monitoring heating, ventilation, air-conditioning and refrigeration equipment; coordinating fans, dampers, valves, heaters and compressors; and exchanging status and control data with a building-management system or supervisory controller. Its Ethernet and RS-485 interfaces allow integration with Modbus and BACnet networks, while the process bus supports Siemens PL-Link devices.

The controller is freely programmed with SAPRO, so its final behavior is defined by the installed application program rather than by a fixed factory sequence. The SD-card interface and USB service connection support application loading, firmware updates, commissioning and archiving.

 

Dimensions, Mounting & Connection Notes

Item Verified Information
Housing color Pigeon blue base plate, RAL 5014; light gray housing, RAL 7035
Weight 468 g
Ingress protection IP20
Signal wiring 0.5–2.5 mm² wire; stranded wire requires terminating sleeves
Screw-terminal stripping length 7 mm
Spring-cage terminal stripping length 10 mm
Ethernet cable Screened Category 5 for 100 BASE-TX or Category 4 for 10 BASE-T
Ethernet length Maximum 100 m
Peripheral-bus length Maximum 30 m overall
Process-bus length Maximum 1000 m overall; maximum 700 m between two nodes
Third-party-bus length Maximum 1000 m at 9.6 kbaud
Service-interface length Maximum 3 m
Signal wiring length Maximum 80 m; NTC10k and NTC100k on X9–X11 are limited to 30 m

The controller uses plug-in terminal blocks. Power must be disconnected before handling the terminals. SELV/PELV circuits and mains-voltage circuits must not share a terminal block, and the controller’s output circuits are not internally fused.

 

FAQ

What is the Siemens POL688.10/STD?
It is a Siemens Climatix C600 freely programmable HVAC&R controller with 27 physical inputs and outputs.

What is the Siemens stock number for POL688.10/STD?
The stock number is S55396-C881-A100.

What power supply does the POL688.10/STD use?
It operates from AC 24 V, -20% to +20%, or DC 24 V, ±10%.

How many inputs and outputs does it have?
It has 27 physical I/O: 3 universal inputs, 8 universal inputs/outputs, 6 digital inputs, 8 relay outputs and 2 triac outputs.

Does the POL688.10/STD include an HMI?
No. The POL688.10/STD is the version without an integrated HMI; the POL688.80/STD includes an integrated HMI.

Which communication protocols are supported onboard?
Onboard interfaces support Modbus, BACnet, PL-Link, JSON and OPC UA, with additional protocol options available through communication modules.

Can the I/O be expanded?
Yes. The controller supports up to 31 Climatix I/O extension modules through its peripheral bus.

Which tools are used to program and commission it?
SAPRO is used for application programming, while SCOPE and the USB service interface are used for commissioning and diagnostics.

What environmental rating does the controller have?
The housing is rated IP20, so the controller must be installed in a protective enclosure.