Sale!

Spectrum Controls 1746SC-INO4I | 4-Channel Isolated Analog Output Module

Parameter Value
Manufacturer Spectrum Controls
Exact model 1746SC-INO4I
Product type Four-channel isolated analog output module
Control-system platform Allen-Bradley SLC 500
Output type Current only
Number of output channels 4, individually isolated
Output ranges 0–20 mA, 0–21 mA, or 4–20 mA
Output resolution 16 bits
Current resolution 366 nA per count
Step response time 1 ms typical to 95% of full scale
Output impedance Greater than 1 MΩ
Categories: , , , , Brand:

Description

Core Product Summary

The Spectrum Controls 1746SC-INO4I is a four-channel isolated analog output module for Allen-Bradley SLC 500 systems. It provides four individually isolated current outputs and is intended for applications that require isolated analog command signals in the SLC 500 I/O architecture.

Each channel can be independently programmed for 0–20 mA, 0–21 mA, or 4–20 mA operation. The module provides 16-bit current-output resolution, 750 VDC channel-to-channel isolation, and 750 VDC field-wiring-to-backplane isolation. It supports extended output ranges, auto-calibration, programmable limits, and safe-state behavior, and can be configured through ladder register settings or RSLogix programming software. The module is factory calibrated and provides on-board ambient-temperature compensation.

 

Key Technical Specifications

Parameter Value
Manufacturer Spectrum Controls
Exact model 1746SC-INO4I
Product type Four-channel isolated analog output module
Control-system platform Allen-Bradley SLC 500
Output type Current only
Number of output channels 4, individually isolated
Output ranges 0–20 mA, 0–21 mA, or 4–20 mA
Output resolution 16 bits
Current resolution 366 nA per count
Step response time 1 ms typical to 95% of full scale
Output impedance Greater than 1 MΩ
Maximum load resistance 500 Ω in current mode
Accuracy at 25 °C 0.08% of full scale
Accuracy at 60 °C 0.10% of full scale
Non-linearity 0.02% of full scale
Channel-to-channel isolation 750 VDC
Field-wiring-to-backplane isolation 750 VDC
Backplane current required 120 mA at 5 V DC; 250 mA at 24 V DC
Backplane power consumption 0.6 W typical
Thermal dissipation 4.5 W maximum
Operating temperature 0 to 60 °C
Storage temperature -40 to 85 °C
Relative humidity 5% to 95%, non-condensing
Module ID code 3521
Calibration Factory calibrated; temperature compensation performed once per minute
Recommended cable Shielded twisted pair, Belden 8761 or equivalent
Certifications UL/cUL Listed ANSI/ISA 12.12.01 (Class I, Div 2, Groups A–D), CE EMC, UKCA, FCC, CMIM

 

Engineering Selection Highlights

  • The 1746SC-INO4I is a current-output module for the Allen-Bradley SLC 500 platform, so it should be selected only where the installed I/O chassis and processor configuration are SLC 500 based.
  • Its four individually isolated current channels allow separate output loops without requiring external analog isolation blocks.
  • The selectable 0–20 mA, 0–21 mA, or 4–20 mA range for each channel makes the module suitable for current-command signals with different zero and span requirements.
  • The 16-bit output resolution and 366 nA-per-count current resolution are relevant when the receiving device requires a fine output signal increment.
  • The 500 Ω maximum load resistance in current mode is a practical wiring constraint that must be checked against the connected receiver and loop resistance.
  • The module supports extended output ranges, programmable limits, and safe states, which should be configured according to the required behavior during a fault or process upset.
  • The module may be installed in any 1746 I/O module slot except slot 0, and its 120 mA at 5 V DC and 250 mA at 24 V DC backplane load must be included in the chassis power-supply calculation.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Control platform Allen-Bradley SLC 500 The module is intended for use with SLC 500 systems.
I/O chassis 1746 I/O chassis Install in any 1746 I/O module slot except slot 0.
Output type Four isolated current outputs The INO4I is current-only; the INO4VI is the voltage/current-output variant.
Output ranges 0–20 mA, 0–21 mA, or 4–20 mA Configure each channel independently for the required current range.
Configuration method Ladder register settings or RSLogix programming software Use the applicable SLC 500 programming environment and module configuration method.
Communication formats Scaled engineering units, scaled for PID, proportional counts, 1746-INO4 format, or user-defined scale Select the format that matches the processor program and receiving device.
Power supply 120 mA at 5 V DC and 250 mA at 24 V DC from the backplane Include the module load in the SLC 500 power-supply calculation.
External 24 V DC supply Optional connection can reduce backplane loading Confirm the installed power arrangement before wiring.
Module identification Module ID code 3521 Use this code when configuring the module in the SLC 500 system.

 

Dimensions, Mounting & Connection Notes

Item Verified information
Chassis location Any 1746 I/O module slot except slot 0
Output channels Four differential, individually isolated current outputs
Isolation 750 VDC channel-to-channel; 750 VDC field wiring to backplane
Backplane power 120 mA at 5 V DC; 250 mA at 24 V DC
External 24 V DC option Can be connected to reduce backplane loading
Recommended cable Shielded twisted pair, Belden 8761 or equivalent
Operating temperature 0 to 60 °C
Storage temperature -40 to 85 °C
Relative humidity 5% to 95%, non-condensing
Thermal dissipation 4.5 W maximum

 

Detailed Product Overview

The Spectrum Controls 1746SC-INO4I is a four-channel isolated analog output module designed for Allen-Bradley SLC 500 systems. It provides four individually isolated current-output channels and is intended to supply analog command signals to compatible field equipment within the SLC 500 I/O architecture.

Each of the four channels can be independently configured for 0–20 mA, 0–21 mA, or 4–20 mA operation. This channel-level configuration allows the module to support mixed current-output requirements within one module. The module provides 16-bit output resolution, with a documented current resolution of 366 nA per count. The step response time is 1 ms typical to 95% of full scale.

The module provides 750 VDC channel-to-channel isolation and 750 VDC isolation between field wiring and the backplane. This isolation arrangement is intended to reduce electrical-noise interaction between channels and to protect the processor and rack from field-side electrical conditions. The module uses sigma-delta conversion, is factory calibrated, and performs temperature compensation once per minute.

Output accuracy is specified as 0.08% of full scale at 25 °C and 0.10% of full scale at 60 °C, with non-linearity of 0.02% of full scale. The output impedance is greater than 1 MΩ, and the maximum load resistance in current mode is 500 Ω. These values should be checked against the connected receiver, loop resistance, and required output span before installation.

The module supports extended output ranges, auto-calibration, programmable limits, and safe states. It can be configured using ladder register settings or RSLogix programming software. Supported communication formats include scaled engineering units, scaled-for-PID values, proportional counts, 1746-INO4 format, and user-defined scaling. The selected format must match the processor program and the requirements of the receiving device.

The module draws 120 mA at 5 V DC and 250 mA at 24 V DC from the backplane. It can also be connected to an external 24 V DC supply to reduce backplane loading. The module may be installed in any 1746 I/O module slot except slot 0. Its module ID code is 3521, which is used when configuring the module in the SLC 500 system.

The 1746SC-INO4I is certified UL/cUL Listed to ANSI/ISA 12.12.01 for Class I, Division 2, Groups A–D, and carries CE EMC, UKCA, FCC, and CMIM markings. The manufacturer recommends shielded twisted-pair cable, such as Belden 8761 or equivalent, for analog-output wiring.

1746SC-INO4I

1746SC-INO4I

Applications & System Role

In an Allen-Bradley SLC 500 control system, the 1746SC-INO4I provides four isolated analog current outputs. It converts controller output data into current signals for compatible field devices, actuators, or control-loop equipment.

The module is used where each output loop requires electrical isolation from the other channels and from the SLC 500 backplane. Its individually programmable output ranges, extended output ranges, programmable limits, and safe-state functions support applications where output behavior must be matched to the connected control device and system-safety requirements.

 

FAQ

What is the Spectrum Controls 1746SC-INO4I?
The Spectrum Controls 1746SC-INO4I is a four-channel isolated analog current-output module for Allen-Bradley SLC 500 systems.

How many output channels does the 1746SC-INO4I provide?
It provides four individually isolated current-output channels.

What output ranges does the 1746SC-INO4I support?
Each channel can be independently configured for 0–20 mA, 0–21 mA, or 4–20 mA operation.

Which SLC 500 chassis slots can accept the 1746SC-INO4I?
The module can be installed in any 1746 I/O module slot except slot 0.

What isolation does the 1746SC-INO4I provide?
It provides 750 VDC channel-to-channel isolation and 750 VDC isolation between field wiring and the backplane.

What is the maximum load resistance for the 1746SC-INO4I current outputs?
The maximum load resistance is 500 Ω in current mode.

How is the 1746SC-INO4I configured?
The module can be configured using ladder register settings or RSLogix programming software.

What is the difference between the 1746SC-INO4I and 1746SC-INO4VI?
The 1746SC-INO4I provides four isolated current outputs only. The 1746SC-INO4VI provides four isolated outputs that can be configured as current or voltage outputs.