The SYMAP ECG-8549 is a SYMAP ECG digital protection and control device for low-, medium-, and high-voltage power systems. The SYMAP ECG product line is configured for power management and generator protection, including differential protection for medium-voltage applications.
The device provides protection, control, measurement, and communication functions in one unit. It uses a graphic LCD front panel, supports analog current- and voltage-transformer inputs, and offers serial and fieldbus communication options including RS-232, RS-422/485, PROFIBUS DP, and Modbus RTU. Exact order-code-specific configuration should be confirmed from the complete SYMAP ECG-8549 identification before integration.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Brand / product family | SYMAP |
| Model | ECG-8549 |
| Product type | Digital protection and control device |
| Application family | SYMAP ECG for power management and generator protection |
| Protection scope | Low-, medium-, and high-voltage power systems |
| Generator protection | Includes differential protection for medium-voltage applications |
| Analog inputs | 17 current and voltage transformer inputs |
| Feeder current inputs | 3 CT inputs |
| Ground-current input | 1 CT input |
| Feeder voltage inputs | 3 PT inputs |
| Busbar voltage inputs | 3 PT inputs for first busbar; 3 PT inputs for second busbar |
| Ground-voltage input | 1 PT input |
| Front-panel display | Graphic LCD |
| Programming / data interface | 1 RS-232 port on front panel |
| Serial communication | 1 RS-422/485 port |
| Fieldbus communication | PROFIBUS DP via RS-485 or fiber-optic port; Modbus RTU |
| Power-supply options | 12–36 V DC, 36–72 V DC, 80–300 V DC, or 60–230 V AC |
| Power consumption | Less than 30 W |
| Front-panel ingress protection | IP54 to IEC 60529 |
| Connection ingress protection | IP10 to IEC 60529 |
Detailed Product Overview
The SYMAP ECG-8549 belongs to the SYMAP ECG family of digital protection and control devices. SYMAP devices combine protection functions, control functions, measurement inputs, and an operator interface in a single unit for electrical power systems.
The ECG configuration is intended for power management and generator protection. Its documented protection scope includes generator applications and differential protection for medium-voltage systems. This makes the product relevant to installations where generator behavior, busbar conditions, feeder currents, and protection coordination must be monitored and controlled from one device.
The SYMAP ECG provides 17 analog inputs for current and voltage transformers. These include three CT inputs for feeder current, one CT input for ground current, three PT inputs for feeder voltage, six PT inputs across two busbar voltage groups, and one PT input for ground voltage. This input structure supports protection functions that require both current and voltage information from multiple points in the electrical system.
Communication is provided through a front-panel RS-232 port for programming and data output, an RS-422/485 port, PROFIBUS DP through either RS-485 or a fiber-optic port, and Modbus RTU. These interfaces allow the relay to be integrated into supervisory control, SCADA, or plant automation systems using supported industrial communication methods.
The device is available with multiple power-supply ranges: 12–36 V DC, 36–72 V DC, 80–300 V DC, or 60–230 V AC. Power consumption is documented as less than 30 W. The front panel is rated IP54, while the connections are rated IP10, under IEC 60529.
The ECG-8549 designation identifies a specific SYMAP ECG order configuration. Because suffixes and order codes can define firmware, supply range, protection package, and hardware configuration, the complete designation should be used when planning replacement, configuration, or system integration.

ECG-8549

ECG-8549
Dimensions, Mounting & Connection Notes
The SYMAP ECG device provides a graphic LCD front panel, a front-panel RS-232 port for programming and data output, and rear connections for analog CT/PT inputs, communication ports, and auxiliary power. The front panel is rated IP54 and the connections are rated IP10 under IEC 60529.
The documented analog input allocation comprises 17 CT and PT inputs: three feeder-current CT inputs, one ground-current CT input, three feeder-voltage PT inputs, three PT inputs for each of two busbar voltage groups, and one ground-voltage PT input.
Exact ECG-8549 enclosure dimensions, weight, panel-cutout requirements, terminal torque values, wire-size limits, and mounting clearances are not available for publication.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Power system | Low-, medium-, and high-voltage power systems | The SYMAP family is documented for these voltage levels. |
| Application configuration | SYMAP ECG for power management and generator protection | Confirm that the ECG-8549 order code includes the required protection package. |
| Current measurement | 3 feeder CT inputs and 1 ground-current CT input | Connect current transformers according to the documented input allocation. |
| Voltage measurement | 3 feeder PT inputs, 6 busbar PT inputs, and 1 ground-voltage PT input | The device provides 17 analog CT/PT inputs in total. |
| Programming | Front-panel RS-232 port | Used for programming and data output. |
| Serial communication | RS-422/485 | Available as a device communication port. |
| Fieldbus communication | PROFIBUS DP via RS-485 or fiber optic; Modbus RTU | Select the interface and medium appropriate to the host automation system. |
| Auxiliary power | 12–36 V DC, 36–72 V DC, 80–300 V DC, or 60–230 V AC | Confirm the supply range fitted to the specific order code. |
| Environmental protection | IP54 front panel; IP10 connections | Apply the appropriate enclosure and installation measures for the connection area. |
FAQ
What is the SYMAP ECG-8549?
It is a SYMAP ECG digital protection and control device for low-, medium-, and high-voltage power systems.
What is the ECG configuration used for?
The SYMAP ECG configuration is intended for power management and generator protection, including differential protection for medium-voltage applications.
How many analog inputs does the SYMAP ECG provide?
It provides 17 analog inputs for current and voltage transformers.
Which communication interfaces are available?
The device provides RS-232, RS-422/485, PROFIBUS DP through RS-485 or fiber optic, and Modbus RTU.
What power-supply options are documented?
Documented options are 12–36 V DC, 36–72 V DC, 80–300 V DC, and 60–230 V AC.
How much power does it consume?
Power consumption is documented as less than 30 W.
What ingress protection does it provide?
The front panel is rated IP54 and the connections are rated IP10 under IEC 60529.
Why is the complete order code important?
The ECG-8549 designation identifies a specific SYMAP ECG configuration; suffixes and order codes can define firmware, supply range, protection package, and hardware configuration.
Documented Performance Data
| Metric | Value/range | Test/operating condition |
|---|---|---|
| Power consumption | Less than 30 W | SYMAP device power consumption |
| Front-panel ingress protection | IP54 | IEC 60529 |
| Connection ingress protection | IP10 | IEC 60529 |
| Analog inputs | 17 | CT and PT inputs for protection functions |

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626