Description
3. Key Technical Specifications
- Dynamic signal inputs: 4 independent, fully programmable channels
- Accepted signals: Acceleration, velocity, displacement (proximity probes), and other dynamic parameters
- Tachometer (speed) inputs: 2 channels (proximity, magnetic pickup, or TTL)
- Processing capabilities: Relative and absolute vibration, Smax, eccentricity, thrust position, absolute/differential housing expansion, dynamic pressure
- Frequency range: Analog DC to 60 kHz (–3 dB)
- Input ranges: DC 0 to ±20 V; AC ±10 V max
- Common mode voltage range: –50 to +50 V
- CMRR: >60 dB at 50 Hz
- Crosstalk: –72 dB
- Input impedance: 200 kΩ
- Front-panel features: BNC connectors for buffered raw signals; status LEDs for processing errors, OK system, and alarms
- Pairing: Requires corresponding IOC4T input/output card
- Versions: Standard, separate circuits, and safety (SIL) versions available
- Form factor: VM600 rack-mount card (hot-swappable)
- Note: Exact hardware revision, firmware, and SIL rating must be confirmed against the unit label and system configuration.
4. Product Introduction
The Vibro-Meter MPC4 (P/N 200-510-076-114) is the central machinery protection card in the VM600 series. It simultaneously monitors up to four dynamic signal inputs and two speed channels, performing real-time multi-parameter processing for critical rotating equipment.
Engineers rely on the MPC4 for continuous protection of turbines, compressors, and other high-value machinery. The card delivers programmable measurement of vibration, position, and related parameters, with buffered outputs and clear front-panel status indication for reliable operation in rack-based VM600 systems.
5. Troubleshooting Quick Reference
| Symptom | Possible Cause | Relevance to this Part | Quick Check Method | Recommendation |
|---|---|---|---|---|
| No measurement or “Not OK” status | Sensor/cable fault or channel configuration error | ✅ High | Check gap voltage / sensor supply and front-panel LEDs | Verify sensor wiring and channel settings; replace if hardware fault confirmed |
| Processing or hardware error LED on | Internal fault or configuration mismatch | ✅ High | Note exact LED pattern and review system diagnostics | Reseat card; update configuration; replace card if error persists |
| Missing or incorrect speed signal | Tachometer input wiring or sensor issue | ✅ High | Verify speed sensor signal at BNC or terminals | Check sensor type, wiring, and configuration |
| Alarms trigger incorrectly | Wrong setpoints, filtering, or hysteresis | ✅ Medium | Review Alert/Danger levels and time delays | Adjust setpoints and filtering to match application |
| No communication with rack / IOC4T | Backplane contact or pairing issue | ✅ High | Confirm IOC4T is present and correctly seated | Reseat both cards; verify rack power and backplane |
| Buffered BNC signal abnormal | Sensor or input circuit problem | ✅ Medium | Scope the raw signal at the front-panel BNC | Isolate to sensor chain or replace MPC4 |
If the fault cannot be isolated, photograph the card (including labels and LEDs), note the exact part number and revision, and contact technical support with system details.

MPC4 200-510-076-114

MPC4 200-510-076-114
6. Frequently Asked Questions (FAQ)
Q: What is the primary function of the MPC4 200-510-076-114?
A: It is the main machinery protection card in the VM600 system. It processes up to four dynamic signals and two speed inputs for real-time protection and monitoring of rotating machinery.
Q: Which sensors can be connected?
A: The dynamic channels accept signals from accelerometers, velocity sensors, and proximity (eddy-current) probes. The tachometer channels support proximity, magnetic pickup, or TTL speed sensors.
Q: Does the MPC4 work alone?
A: No. It operates as a card pair with a corresponding IOC4T input/output card in a VM600 rack.
Q: Is the card hot-swappable?
A: Yes. The MPC4 is designed for hot-swap replacement within a powered VM600 rack (follow proper safety and system procedures).
Q: Are there different versions of the MPC4?
A: Yes. Standard, separate-circuits, and safety (SIL) versions exist. Confirm the exact variant required for your application, especially for functional safety systems.
Q: Can it measure both vibration and position?
A: Yes. The programmable channels support relative/absolute vibration, thrust position, eccentricity, Smax, and related parameters.
Q: What condition and warranty do you offer?
A: We supply New Original / New Surplus stock. Units are inspected for basic functionality. Standard coverage is a 1-year warranty against defects. Provide the complete part number 200-510-076-114 (and any revision or SIL marking) when ordering or requesting support.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626