Description
Core Product Summary
The VIBRO-METER VM600 IOCN 200-566-000-113 is the input/output card that forms the second half of the CPUM/IOCN card pair in the VM600 series from Meggitt’s Vibro-Meter product line. Together, the CPUM modular CPU card and the IOCN act as the rack controller and communications interface for a VM600 rack-based machinery protection system (MPS) and/or condition monitoring system (CMS). The IOCN is a single-width card installed in the rear of the rack, in the slot directly behind its associated CPUM.
The card carries the pair’s physical communications interfaces: one primary Ethernet connector (RJ45) for VM600 MPSx software communication and Modbus TCP or PROFINET, one secondary Ethernet connector for redundant Modbus TCP communications, one primary serial connector (RJ11/RJ25) for direct connection to the MPSx software, and two pairs of serial connectors that can configure multi-drop RS-485 networks of VM600 racks. All inputs are protected against electromagnetic interference and signal surges and are EMC compliant. The CPUM/IOCN pair is used with VM600 ABE04x system racks and is the original version of the VM600 rack controller card pairs, supporting the front-panel display and Modbus RTU/TCP and PROFINET communications.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Product type | Input/output card; I/O interface for the CPUM modular CPU card |
| System family | VIBRO-METER (Meggitt) VM600 MPS / CMS platform |
| Order number | 200-566-000-113 (IOCN family; other 200-566 order codes denote other configurations) |
| Card pair | CPUM/IOCN rack controller and communications interface card pair |
| Card format | Single-width card occupying one VM600 rack slot |
| Installation | Rear of a VM600 ABE04x system rack, in the slot directly behind the associated CPUM (slot 0) |
| Backplane connection | Two connectors, direct to the rack backplane |
| Primary Ethernet | One 8P8C (RJ45) connector for VM600 MPSx software communication and/or Modbus TCP and/or PROFINET communications |
| Secondary Ethernet | One 8P8C (RJ45) connector for redundant Modbus TCP communications |
| Primary serial | One 6P6C (RJ11/RJ25) connector for direct connection to the VM600 MPSx software |
| Auxiliary serial | Two pairs of 6P6C (RJ11/RJ25) connectors configurable for multi-drop RS-485 networks of VM600 racks |
| Input protection | All inputs protected against electromagnetic interference (EMI) and signal surges; EMC compliant |
| Communications supported by the card pair | Modbus RTU/TCP, PROFINET; front-panel display on the CPUM |
| Position in VM600 card-pair range | CPUM/IOCN is the original CPUx/IOCx rack controller version (order numbers of the 200-595 / 200-566 series) |
Engineering Selection Highlights
- Fixed pairing with the CPUM — the IOCN is the dedicated I/O interface for the CPUM card and must be installed in the rear of the rack directly behind it; the pair together, not the CPUM alone, provides the system controller and data communications gateway functions.
- Single-width rear-slot footprint — unlike the double-width CPUM, the IOCN occupies one slot at the rear of the rack, so its space planning is independent of the front-of-rack slot allocation.
- Dual Ethernet with redundant Modbus TCP — the primary RJ45 serves MPSx networking plus Modbus TCP or PROFINET, and the secondary RJ45 provides redundant Modbus TCP; systems requiring communications availability should plan both links from the outset.
- Multi-drop RS-485 rack networking — the two pairs of serial connectors allow several VM600 racks to be configured as a multi-drop RS-485 network, which is the integration path for multi-rack monitoring installations without adding external gateways.
- Direct local service connection — the primary serial connector supports a direct connection to a PC running the VM600 MPSx software, giving commissioning and service staff a local configuration and diagnostics path independent of the plant network.
- Version selection within the CPUx/IOCx range — CPUM/IOCN is the original rack controller version with front-panel display and Modbus RTU/TCP and PROFINET support; other versions in the same family (CPUR/IOCR and CPUR2/IOCR2) provide rack controller redundancy or fieldbus data processing with different protocol support, so the card pair version must match the system’s functional requirements.
- Order code precision — the IOCN family spans multiple 200-566 order codes; replacements should be matched by the complete order code rather than by the IOCN name alone.

VM600 IOCN 200-566-000-113

VM600 IOCN 200-566-000-113
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Companion card | CPUM modular CPU card (200-595 series) | The CPUM is a double-width card at the front of the rack (slots 0 and 1); the IOCN installs behind it at the rear (slot 0). |
| Rack | VM600 ABE04x system racks | The CPUM/IOCN card pair is used with ABE04x racks; the CPUM may also be used alone without an IOCN where the application allows. |
| Backplane | Two direct connectors per card | Each card of the pair connects directly to the rack backplane. |
| Configuration software | VM600 MPSx software | Reachable via the card’s Ethernet interfaces or the primary serial direct connection. |
| Fieldbus protocols | Modbus TCP, PROFINET (Ethernet); Modbus RTU supported by the card pair | Primary Ethernet carries MPSx plus Modbus TCP or PROFINET; secondary Ethernet carries redundant Modbus TCP. |
| Multi-rack networking | Two pairs of auxiliary serial connectors for multi-drop RS-485 networks of VM600 racks | Enables cascaded communication between multiple racks. |
| System functions provided by the CPUx/IOCx pair | Configuration management, hot-swapping with automatic reconfiguration, front-panel display, alarm reset (AR) button, system and measurement event logging, MPS rack security, fieldbus communications and/or communications redundancy | The exact combination depends on the card pair version; CPUM/IOCN provides the original function set with front-panel display and Modbus RTU/TCP and PROFINET. |
| Related system components | VM600 rack, rack power supply, monitoring card pairs (e.g., MPC4/IOC4T, AMC8/IOC8T, XMx16/XIO16T), RLC16 relay card | The rack controller pair is an optional functional layer added to a VM600 rack of monitoring cards. |
Dimensions, Mounting & Connection Notes
- The IOCN is a single-width card occupying one VM600 rack slot; it is installed at the rear of the ABE04x rack in the slot directly behind its associated CPUM card (slot 0).
- Each card of the pair connects directly to the rack backplane using two connectors.
- Communications connectors on the card: two 8P8C (RJ45) Ethernet connectors (primary for MPSx/Modbus TCP/PROFINET, secondary for redundant Modbus TCP) and 6P6C (RJ11/RJ25) serial connectors (one primary for direct MPSx connection, two pairs for multi-drop RS-485 rack networks).
- All inputs are protected against electromagnetic interference and signal surges and comply with EMC requirements.
- The primary Ethernet connector on the IOCN is used instead of the CPUM’s own NET connector for the primary Ethernet connection.
Detailed Product Overview
The VM600 platform organizes its rack functions as card pairs, and the IOCN belongs to the most important of them: the CPUx/IOCx rack controller and communications interface pair. The name says what it is — an input/output card in the network sense (hence IOCN, Input Output Communication Network) — and its job is to carry the communications and interface load of its partner card, the CPUM.
The pairing is architecturally fixed. The CPUM is a double-width card at the front of the rack in slots 0 and 1; the IOCN is a single-width card installed at the rear of the rack in the slot directly behind it. Both cards connect to the backplane through two connectors each. The division of labor is clean: the CPUM holds the processing, the LCD display, the keys, and the alarm reset button; the IOCN holds the connectors through which the pair communicates. This split also explains a service consideration — a rack communication failure may sit on either card of the pair, so diagnostics should address both.
The connector set defines the card’s integration value. The primary Ethernet connector (RJ45) carries communication with the VM600 MPSx software and Modbus TCP or PROFINET traffic — this is the main path between the rack and the plant’s higher-level systems. The secondary Ethernet connector provides redundant Modbus TCP, so a communications link failure does not isolate the rack. The primary serial connector (RJ11/RJ25 type) supports a direct point-to-point connection to a PC running MPSx, which is useful during commissioning or when the plant network is unavailable. The two pairs of auxiliary serial connectors extend the card’s role to multi-rack systems: they can be configured as a multi-drop RS-485 network that links several VM600 racks, giving larger installations a shared communications path without additional hardware per rack.
All of the card’s inputs are protected against electromagnetic interference and signal surges and are EMC compliant — a practical necessity for communications wiring that often runs alongside power circuits in equipment rooms.
Selection within the product family deserves attention. CPUM/IOCN is the original version of the rack controller pair, identified by 200-595-series (CPUM) and 200-566-series (IOCN) order numbers, and provides the front-panel display plus Modbus RTU/TCP and PROFINET support. The same family includes versions with different capabilities: a version with rack controller redundancy (CPUR/IOCR) and a version with mathematical processing of fieldbus data and Modbus TCP plus PROFIBUS DP support (CPUR2/IOCR2). Because these versions differ in supported functions and protocols, the card pair version is a system-level design decision, not an interchangeable choice — and the 200-566-000-113 code identifies a specific configuration of the IOCN within the CPUM/IOCN version.
For procurement, the practical rules follow from the architecture: match the complete order code when replacing, confirm the CPUM/IOCN pairing in the target rack, and verify after installation that MPSx connectivity, fieldbus communications, and (if used) the RS-485 multi-rack network all resume correctly.
Applications & System Role
In a VM600 installation, the IOCN occupies the communications interface layer of the rack controller pair. Its associated CPUM executes the rack controller function — configuration management, event logging, front-panel display — while the IOCN provides the physical I/O through which that function reaches the outside world: the plant network carrying Modbus TCP or PROFINET data to DCS and SCADA systems, the redundant Ethernet link protecting communications availability, the local serial service connection, and the RS-485 multi-drop links that tie several VM600 racks into one network.
A VM600 rack-based monitoring system is used for the protection and monitoring of rotating machinery — typically large machines such as gas, steam, and hydro turbines and generators, smaller machines such as compressors, fans, motors, and pumps, and balance-of-plant equipment — where a centralized monitoring system with a medium to large number of measurement points is required. Within such an installation, the CPUM/IOCN pair is the optional rack controller layer added on top of the monitoring card pairs, turning a collection of protection positions into a networked, centrally configurable system.
The card is therefore specified when a VM600 rack needs remote configuration, fieldbus integration, or multi-rack networking — and it is the component whose replacement restores those functions when a rack loses its network connectivity while protection cards continue running locally.
FAQ
What is the VIBRO-METER VM600 IOCN 200-566-000-113?
It is the input/output communication card that pairs with the CPUM modular CPU card, forming the rack controller and communications interface card pair for VM600 machinery protection (MPS) and condition monitoring (CMS) systems.
Where is it installed?
It is a single-width card installed at the rear of a VM600 ABE04x system rack, in the slot directly behind its associated CPUM card (slot 0), connecting to the backplane through two connectors.
What interfaces does it provide?
One primary Ethernet (RJ45) for MPSx and Modbus TCP or PROFINET, one secondary Ethernet (RJ45) for redundant Modbus TCP, one primary serial connector for a direct MPSx connection, and two pairs of serial connectors for multi-drop RS-485 networks of VM600 racks.
Can it link multiple VM600 racks together?
Yes — its two pairs of auxiliary serial connectors can be configured as a multi-drop RS-485 network connecting several VM600 racks.
Can the CPUM work without an IOCN?
A CPUM card can be used either alone or with an associated IOCN card as a pair, depending on the application and system requirements; the IOCN adds the extended communications interfaces of the pair.
Which protocols does the CPUM/IOCN pair support?
The CPUM/IOCN pair is the original rack controller version, supporting Modbus RTU/TCP and PROFINET communications together with a front-panel display.
What protections does the card have?
All inputs are protected against electromagnetic interference and signal surges, and the card complies with EMC requirements.
Can it replace any IOCN card?
Not by name alone — the IOCN family includes multiple 200-566 order codes for different configurations, so replacements should be matched by the complete order code and verified against the rack configuration.