Sale!

Woodward SPM-D11 Microprocessor-Based Synchronizer & Load Share Unit

The Woodward SPM-D11 is a microprocessor-based synchronizer and load-sharing unit engineered for single-phase and three-phase AC generators operating with Woodward or third-party speed controls and automatic voltage regulators (AVRs). The unit provides automatic frequency, phase angle, and voltage matching across a single circuit breaker, combining precise synchronization routines with integrated real power control, power factor regulation, and generator protection functions.

Categories: , , , , , SKU: SPM-D11 Brand:

Description

Core Product Summary (Brand / Model / Key Attributes)

The Woodward SPM-D11 is a microprocessor-based synchronizer and load-sharing unit engineered for single-phase and three-phase AC generators operating with Woodward or third-party speed controls and automatic voltage regulators (AVRs). The unit provides automatic frequency, phase angle, and voltage matching across a single circuit breaker, combining precise synchronization routines with integrated real power control, power factor regulation, and generator protection functions.

Designed for panel mounting, the module features two-phase voltage sensing for both the generator and busbar, single-phase generator current sensing (1 A or 5 A CTs), and configurable analog and discrete bias outputs. It incorporates a front-panel two-line liquid crystal display, an integrated digital synchroscope, and multi-level password protection for secure field parameterization and live operational monitoring.

 

Key Technical Specifications

Specification Value / Detail
Product Type Microprocessor-Based Synchronizer & Load Control Unit
Model Reference SPM-D11 / SPM-D11 Series
Order Numbers 8440-1666, 8440-1705, 8440-1706, 8440-1715 (Model dependent)
Power Supply Input 12 VDC / 24 VDC nominal (18–32 VDC operational range)
Voltage Measurement Inputs 2-phase generator sensing, 2-phase busbar sensing (100 VAC or 400 VAC configurable)
Current Measurement Input Single-phase generator CT sensing (../1 A or ../5 A rated)
Measuring Frequency Range 40 Hz to 70 Hz
Bias Control Outputs Freely configurable analog outputs (±1 V, ±3 V, ±5 V, ±10 V, 0–5 V, 0–20 mA, ±20 mA) & PWM output (500 Hz)
Discrete Control Outputs Raise/Lower relay outputs for speed and voltage adjustment
Protective Functions (ANSI) Over/Undervoltage (59/27), Over/Underfrequency (81O/U), Reverse/Reduced Power (32R/F), Overload (32)
Front Interface 2-line LCD display, digital synchroscope, status LEDs, and navigation keys
Operating Temperature -20 °C to +70 °C

 

Detailed Product Overview

The Woodward SPM-D11 serves as a central synchronizing and load control module within generator set power management architectures. By continuously sampling generator and busbar potential transformers (PTs) along with generator current transformer (CT) signals, the unit computes frequency slip, voltage differential, and phase angle displacement in real time. It issues continuous bias corrections to the engine governor and AVR to bring the generator into precise phase alignment before commanding circuit breaker closure.

In addition to phase-matching and slip-frequency synchronizing modes, the SPM-D11 manages active power (kW) and reactive power (kVAR) distribution during mains-parallel operation or isolated load sharing. The unit embeds protective relaying to safeguard the generator against electrical abnormalities—including reverse power conditions, overcurrent, and voltage/frequency deviations—reducing overall control cabinet hardware requirements by combining control and protection into a single module.

 

Engineering Selection Highlights

  • Single-Breaker Synchronizing: Automates generator-to-busbar or generator-to-mains synchronization across a single circuit breaker.
  • Universal Bias Output Compatibility: Provides configurable analog voltage/current outputs and PWM signals to interface seamlessly with diverse speed governors and AVRs.
  • Integrated Generator Protection: Includes built-in ANSI protection curves (27/59, 81O/U, 32R/F, 32) to prevent reverse power flow and electrical out-of-spec operation.
  • Isochronous Load Sharing & Power Factor Control: Supports base load, power factor (VAR) control, and real-power load management during parallel generator operation.
  • Dual Parameterization Methods: Parameters can be configured directly via the front keypad and LCD screen or externally using a connected PC running Woodward configuration software.
SPM-D11

SPM-D11

SPM-D11

SPM-D11

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Speed Governor Interface Compatible with Woodward and third-party electronic governors Connects via analog bias (e.g., ±5 V, 0–20 mA) or 500 Hz PWM speed bias signals
AVR Interface Compatible with standard Automatic Voltage Regulators Utilizes configurable analog voltage bias or discrete Raise/Lower relay signals
Instrument Transformers 100 VAC or 400 VAC PTs; 1 A or 5 A CTs Voltage inputs require 2-phase sensing on generator and bus sides
Control Power 18–32 VDC power supply Requires proper external fusing on the primary DC input terminals

 

Dimensions, Mounting & Connection Notes

  • Mounting Configuration: Flush-mount panel enclosure designed for cutout installation on control cabinet door panels or internal swing frames.
  • Terminal Connections: Rear-mounted pluggable screw terminal blocks handle AC voltage sensing, CT current loops, DC power inputs, and discrete control wiring.
  • CT Wiring Precautions: Ensure generator CT secondary circuits are securely grounded at one point and never open-circuited while primary current is flowing.

 

FAQ

What is the Woodward SPM-D11?

The Woodward SPM-D11 is a microprocessor-based synchronizer and load-sharing unit used to match speed, phase, and voltage between an AC generator and a busbar before closing the circuit breaker.

What protective functions are built into the SPM-D11?

The module includes over/undervoltage (59/27), over/underfrequency (81O/U), reverse/reduced power (32R/F), and generator overload (32) protection functions.

How does the SPM-D11 control generator speed and voltage?

It issues corrections via freely configurable analog bias outputs (voltage or current), 500 Hz PWM outputs, or discrete Raise/Lower relay contacts wired to the engine governor and AVR.

What voltage and current sensing options does it support?

The SPM-D11 supports 2-phase AC voltage sensing (100 VAC or 400 VAC nominal) for both generator and busbar, alongside single-phase CT current sensing (1 A or 5 A).

 

Verification & Troubleshooting Notes

  • Front Panel Synchroscope: Utilize the built-in digital synchroscope display to visually monitor phase angle difference and frequency slip during manual test synchronization routines.
  • Bias Output Polarity Check: If speed or voltage diverges during synchronization attempts, verify that output bias range, offset, and gain parameters match the input impedance and polarity requirements of the connected governor or AVR.
  • Voltage/Frequency Phase Matching: Confirm that potential transformer (PT) phase wiring matches between the generator and busbar inputs to prevent out-of-phase closure attempts.