Sale!

Woodward SPM-D1115BLSXR Load Share Synchronizer

The Woodward SPM-D1115BLSXR is a microprocessor-based load share synchronizer designed for single or three-phase AC generator sets equipped with compatible speed controls and automatic voltage regulators. Part of the versatile SPM-D11 product series, this controller combines automated circuit breaker synchronization, real power and power factor control, isochronous load/var sharing, and core generator protection features into a compact panel-mounted unit.

Categories: , , , , SKU: SPM-D1115BLSXR Brand:

Description

Core Product Summary (Brand / Model / Key Attributes)

The Woodward SPM-D1115BLSXR is a microprocessor-based load share synchronizer designed for single or three-phase AC generator sets equipped with compatible speed controls and automatic voltage regulators. Part of the versatile SPM-D11 product series, this controller combines automated circuit breaker synchronization, real power and power factor control, isochronous load/var sharing, and core generator protection features into a compact panel-mounted unit.

Engineered for precision power management, the unit supports phase-matching or slip-frequency synchronization alongside continuous voltage matching. Equipped with the LSXR package variant, it provides flexible analog and discrete bias outputs for speed and voltage control, comprehensive single-phase current transformer (CT) sensing, and two-phase voltage measurements for both the generator and the bus. Operator interface features include a clear two-line liquid crystal display, an integrated digital synchroscope, and multi-level password protection configured either locally via the front panel or through dedicated PC software.

 

Key Technical Specifications

Specification Category Verified Technical Parameter / Value
Product Type / Series Woodward SPM-D11 Series Load Share Synchronizer
System Compatibility 1-phase or 3-phase AC generators with compatible speed controls and AVRs
Voltage Measuring Inputs Two-phase sensing for generator and busbar
Current Measuring Inputs Single-phase CT sensing for generator
Synchronization Modes Phase match or slip frequency synchronization with voltage matching; synchro-check
Parallel Operation Features Real power control, soft unloading, power factor control, and isochronous load/var sharing
Control Outputs (LSXR Package) Configurable analog bias outputs for voltage and speed, 500 Hz PWM speed bias output, and discrete raise/lower relay outputs
Generator Protection Functions (ANSI) Over-/undervoltage (59/27), over-/underfrequency (81O/U), reverse/reduced power (32R/F), and generator overload (32)
Display & User Interface Two-line liquid crystal display, digital synchroscope, status LEDs, and pushbuttons
Configuration Interface Direct front-panel access or via PC connection
Compliance & Approvals CE marked, UL/cUL listed

 

Detailed Product Overview

The Woodward SPM-D1115BLSXR operates as an integrated management node within power generation architectures, bridging the gap between engine governing systems, automatic voltage regulators, and switchgear circuit breakers. By handling both synchronization and load distribution, it eliminates the need for standalone synchronizers and separate load-sharing modules in basic paralleling applications.

The controller continuously monitors busbar and generator parameters through two-phase voltage inputs and single-phase current inputs. When paralleling conditions are met, it issues precise control adjustments via its advanced LSXR interface package. This package features highly flexible analog bias outputs capable of adapting to various voltage and current control levels, alongside pulse-width modulation (PWM) and discrete relay outputs. This ensures smooth transitions during synchronizing, clean breaker closure, and stable real-power and reactive-power (var) sharing once tied to the grid or to a common bus.

Beyond paralleling tasks, the unit provides integral generator safety monitoring. It tracks abnormal operational thresholds such as voltage spikes, frequency drift, reverse power flow, and system overloads, executing protective actions when limits are exceeded. Configuration flexibility allows engineers to adjust parameters locally using the front-panel display or configure complex setups via software tools, making it adaptable to diverse standby, prime power, and marine installations.

 

Engineering Selection Highlights

  • Integrated Dual Functionality: Combines automated synchronizing for a single circuit breaker with real power/var load sharing and protective relay functions in one hardware device.
  • Flexible Bias Output Options (LSXR): Equipped with configurable analog levels, PWM speed bias, and discrete raise/lower outputs to interface seamlessly with varied electronic governors and AVRs.
  • Comprehensive System Sensing: Utilizes two-phase voltage sensing for both generator and bus signals alongside single-phase CT inputs to ensure reliable synchronization decisions.
  • Built-in Protective Monitoring: Features standard ANSI-compliant protection monitoring parameters—including over/undervoltage, over/underfrequency, and reverse power—reducing reliance on external protective relays for basic setups.
  • Direct Diagnostics: Features a built-in digital synchroscope and a two-line LCD text interface that display real-time operational status, breaker states, and diagnostic alarms without requiring external meters.
SPM-D1115BLSXR

SPM-D1115BLSXR

System Compatibility & Integration Requirements

| Item / Dependency | Verified Compatibility or Requirement | Practical Note | |—|—| | Governor / Speed Control | Compatible with Woodward and other electronic speed controls accepting analog or discrete bias signals | Verify input signal type matches the chosen LSXR configuration setting. | | Automatic Voltage Regulator (AVR) | Compatible with standard AVRs featuring external voltage adjustment or analog bias inputs | Allows automated voltage matching prior to breaker closure. | | Voltage Transformers (PT) | Two-phase voltage measurement architecture | Requires properly rated potential transformers matching system nominal voltages. | | Current Transformers (CT) | Single-phase CT sensing input | Ensure correct secondary rating (typically ../1A or ../5A depending on model subclass configuration). | | Configuration Tool | PC-based software configuration utility or front-panel menu | Enables precise tuning of control loops, dead times, and protection thresholds. |

 

Dimensions, Mounting & Connection Notes

  • Enclosure Standard: Designed for standard panel cutout dimensions conforming to DIN housing specifications (APRANORM DIN 43 700).
  • Mounting Method: Flush panel mounting secured via mounting clamps to ensure front-face environmental sealing.
  • Wiring Terminations: Plug-in screw terminal blocks for discrete inputs, relay outputs, power supply, and communication lines. Separate high-voltage measurement paths (VT/CT lines) from low-voltage control wiring.
  • Grounding: Maintain proper shielding on signal and communication cables to protect against electromagnetic interference (EMI) in heavy industrial switchgear environments.

 

FAQ

What is the Woodward SPM-D1115BLSXR?

It is a microprocessor-based digital synchronizer and load-sharing controller designed for AC generator sets, handling automated breaker synchronization, power distribution, and generator protection.

Which product family does this unit belong to?

It belongs to the Woodward SPM-D11 series of generator control and synchronizing units.

What primary job does the LSXR designation indicate?

The LSXR suffix denotes a specific hardware and software package configuration that provides advanced analog bias outputs, PWM speed control capabilities, and discrete relay options for comprehensive speed and voltage management.

What types of synchronization does the module support?

It supports phase-matching or slip-frequency synchronization paired with automatic voltage matching, as well as a dedicated synchro-check function.

Does the unit provide generator protections?

Yes, it incorporates standard protection functions including over-/undervoltage, over-/underfrequency, generator overload, and reverse or reduced power detection.

How is the SPM-D1115BLSXR configured?

Parameters can be adjusted directly via the front-panel pushbuttons and LCD menu or configured externally using a computer connection.

 

Verification & Troubleshooting Notes

  • Display Error Indication: Check the two-line LCD screen for active alarm messages or configuration error flags if the unit refuses to initiate synchronization sequences.
  • Phase Matching Failures: If synchronization does not complete, verify that generator and busbar voltage transformer phase rotations, nominal voltages, and frequency matching parameters are correctly configured.
  • Control Output Response: Ensure that the analog or discrete bias output configuration matches the exact input requirements of the connected electronic governor or AVR.
  • Sensing Integrity: Confirm that CT and PT wiring connections are secure and that scaling parameters match primary/secondary transformer ratios to prevent erratic power calculation or protection tripping.