Description
Core Product Summary
The ABB PL810 (order number 3BDH000311R0101) is a Power Link Module used with the LD 800P DP/PA Linking Device. It connects a single non-intrinsically safe PROFIBUS PA segment to a Head Station (HS 810, HS 820 or HS 840).
The module supplies the PROFIBUS PA bus at 24–26 V DC with a maximum current of 400 mA and operates at the standard PA baud rate of 31.25 kbit/s. It includes a fixed bus termination and requires no configuration. Up to 32 PROFIBUS PA devices can be connected to one segment.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Product type | Power Link Module |
| Order number | 3BDH000311R0101 |
| Model | PL810 |
| System | LD 800P DP/PA Linking Device |
| PROFIBUS PA baud rate | 31.25 kbit/s (IEC 61158-2) |
| PA supply voltage | 24 … 26 V DC |
| PA supply current | ≤ 400 mA |
| Number of PA devices | Up to 32 per segment |
| Module supply voltage | 20 … 35 V DC |
| Ambient temperature | –20 … +60 °C |
| Protection class | IP20 |
| Dimensions (approx.) | 80 × 115 × 107 mm |
| Weight (approx.) | 320 g |
| Bus termination | Fixed, integrated |
| Configuration | None required |
Engineering Selection Highlights
- Forms the PA-side interface of the LD 800P Linking Device when combined with a compatible Head Station (HS 810 / HS 820 / HS 840).
- Supplies a non-intrinsically safe PROFIBUS PA segment at 31.25 kbit/s with up to 400 mA.
- Supports up to 32 PROFIBUS PA field devices on one segment.
- Integrated fixed bus termination simplifies segment installation.
- No parameterization or programming is required.
- Approved for installation in Zone 2 / Div. 2 hazardous areas.
- Removable terminals facilitate wiring and maintenance.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Head Station | HS 810, HS 820 or HS 840 | Mandatory; forms LD 800P Linking Device |
| PROFIBUS PA segment | Non-intrinsically safe, 31.25 kbit/s | One segment per PL810 module |
| PA device count | Maximum 32 devices | Limited by segment current and topology |
| Power supply | 20 … 35 V DC for module; 24 … 26 V DC for PA bus | Separate supplies as specified |
| Mounting | Power rail (PR 900-N series) or suitable DIN-rail arrangement | Compatible with LD 800P accessories |
| Hazardous area | Zone 2 / Div. 2 | ATEX approval |

PL810 3BDH000311R0101

PL810 3BDH000311R0101
Detailed Product Overview
The ABB PL810 (3BDH000311R0101) is a Power Link Module designed exclusively for use with the LD 800P family of DP/PA Linking Devices. When combined with a Head Station (HS 810, HS 820 or HS 840) it creates a complete DP-to-PA gateway.
The module generates a single non-intrinsically safe PROFIBUS PA segment operating at the standard 31.25 kbit/s baud rate defined by IEC 61158-2. It provides bus power of 24–26 V DC with a maximum current of 400 mA, sufficient for a typical segment of up to 32 field devices. A fixed 100 Ω bus termination is permanently integrated, eliminating the need for an external terminator at the module end.
No configuration or software parameterization is required. Communication between the Power Link Module and the Head Station is established via a simple wired link on designated terminals. The module features removable terminals for convenient installation and service.
Electrical isolation is provided between the various circuits. The unit is rated for ambient temperatures from –20 °C to +60 °C and carries IP20 protection. It is approved for installation in Zone 2 / Div. 2 hazardous locations under ATEX.
The PL810 is selected when a non-IS PROFIBUS PA segment must be added to an existing or new LD 800P Linking Device installation. Correct matching with a compatible Head Station and adherence to PROFIBUS PA segment design rules (cable length, device current draw, and topology) are essential for reliable operation.
Applications & System Role
The PL810 Power Link Module is the PA-side component of the ABB LD 800P DP/PA Linking Device. It converts the PROFIBUS DP connection provided by a Head Station into a PROFIBUS PA segment that can power and communicate with field devices.
In process automation architectures it enables the connection of PROFIBUS PA instruments (transmitters, actuators, etc.) to a higher-level PROFIBUS DP network. Typical use is in process plants where field devices on the PA bus must be integrated into a control system via a DP/PA coupler.
FAQ
What is the ABB PL810 3BDH000311R0101?
It is a Power Link Module that forms part of the LD 800P DP/PA Linking Device and connects one non-intrinsically safe PROFIBUS PA segment.
Which Head Stations can be used with the PL810?
It must be operated together with an HS 810, HS 820 or HS 840 Head Station.
What is the PROFIBUS PA baud rate?
The PA segment operates at 31.25 kbit/s.
How many PROFIBUS PA devices can be connected?
Up to 32 devices can be connected to one PA segment.
Does the module require configuration?
No configuration or programming is required.
What power does the PA segment receive?
The module supplies 24–26 V DC at a maximum of 400 mA and includes a fixed bus termination.